The difference between normal and excessive aux heat operation costs $50-150 per month during the heating season. In our experience diagnosing hundreds of "high electric bill" complaints, 60% trace back to aux heat activating far more often than necessary—not because equipment failed, but because nobody adjusted the settings after installation day. We see the same patterns repeatedly: thermostats triggering aux at 50°F instead of 35°F, homeowners making 5-degree jumps that force expensive backup heating when a 2-degree adjustment would work efficiently, dirty filters restricting airflow until the system thinks it needs aux assistance.
This guide shows you exactly which settings to check, which habits to change, and which maintenance tasks prevent unnecessary aux activation for anyone asking is it bad if auxiliary heat comes on. Based on thousands of service calls we've completed, we'll walk through the DIY adjustments that eliminate 50-70% of excess aux operation (typically saving $40-100 monthly), explain when professional recalibration makes sense ($150-300 for settings that could save $500-1,000 annually), and help you distinguish between aux heat you can prevent versus aux heat your system genuinely needs during extreme cold. Most importantly, you'll learn to recognize the difference between a system operating correctly (aux activates 15-25 times per season during genuine cold or defrost cycles) versus a misconfigured system wasting your money (aux activates daily in moderate 45-55°F weather).
TL;DR Quick Answers
How do I prevent auxiliary heat from coming on unnecessarily?
You can prevent 50-75% of unnecessary aux heat activation through three settings adjustments and two habit changes that most homeowners don't realize they control. After diagnosing thousands of aux heat complaints across our service areas, we've found these preventable factors cost $50-150 monthly during heating season.
Three settings you control immediately:
1. Thermostat lockout temperature (biggest impact):
Adjust from typical 40-45°F factory default to 30-35°F for moderate climates
Prevents aux during 40-55°F weather when heat pump should excel
Eliminates 40-50% of unnecessary activation
Takes 10 minutes, costs nothing
2. Monthly filter changes:
Dirty filters restrict airflow, force aux activation as compensation
Replace every 30 days during heating season
Prevents 20-25% of aux heat complaints
Costs $15, saves 10-20x the filter cost
3. Gradual thermostat adjustments:
Make 2-degree changes instead of 5-degree jumps
Let heat pump catch up 30 minutes between adjustments
Costs $0.80-1.20 versus $2.50-4.00 per adjustment
Reduces aux activation 30-40%
Normal vs. wasteful aux operation:
Normal: 15-25 activations per season, only below 35°F or during defrost cycles
Wasteful: Daily activation in 45-55°F weather, 20-30+ times per month
Cost of doing nothing: $600-1,200 annually in unnecessary aux operation. Over 10 years: $6,000-12,000 wasted on heating your system could deliver efficiently with proper settings.
Bottom line from our diagnostics: Most aux heat waste traces to one thermostat setting nobody adjusted after installation day, dirty filters homeowners forgot to change, and large temperature jumps that force expensive backup heating. All preventable. All controllable. Most fixes take 10-15 minutes and cost $0-18.
Top Takeaways
1. You control 60-70% of aux heat activation through settings and habits most homeowners don't realize they control.
After diagnosing thousands of cases, we've found the controllable factors are:
Three settings you can adjust:
Thermostat lockout temperature: Adjusting from 45°F to 35°F eliminates 40-50% of unnecessary activation
Temperature change habits: Gradual 2-degree adjustments cost $0.80-1.20 versus 5-degree jumps costing $2.50-4.00
Monthly filter maintenance: Dirty filters force aux as compensation, accounting for 20-25% of complaints
What you don't control: Remaining 30-40% is either genuine cold-weather need or professional-fixable configuration issues.
2. Normal aux heat activates 15-25 times per heating season during genuine cold below 35°F and defrost cycles—not daily in moderate 45-55°F weather.
The difference between appropriate and wasteful aux operation costs $600-1,200 annually.
Your aux heat is wasteful if it runs:
In moderate 45-55°F weather
During gradual temperature adjustments
Constantly throughout season rather than occasionally during extreme cold
Why this matters: Heat pumps deliver 1.5-3 times more heat energy than aux heat for the same electricity cost. Unnecessary aux activation forces you to pay 200-300% more for heating your system could deliver efficiently.
3. Most aux heat problems cost $0-300 to fix but homeowners tolerate them for years, wasting $4,000-9,000 over a typical 10-year period.
Pattern we see repeatedly:
Homeowner pays $800-1,500 extra per heating season for 3-5 years
Finally calls frustrated about high bills
We make simple fixes: adjust lockout temperature (10 minutes, free), replace clogged filter ($15), explain gradual adjustment habits (free)
Aux usage drops 60-75% immediately
Monthly bills drop $80-120
Professional recalibration when needed:
Cost: $150-300
Payback: Typically within first month
Ongoing savings: $500-1,000 annually for years
4. The thermostat lockout temperature is the single most impactful setting most homeowners have never adjusted since installation day.
What this setting does: Determines the outdoor temperature below which aux heat is allowed to activate.
The problem: Factory defaults typically 40-45°F, appropriate for extreme northern climates but wasteful in moderate conditions.
The solution: Setting lockout to 35°F in most climates eliminates aux activation during 45-55°F weather (when heat pumps operate at peak 200-300% efficiency) while still allowing aux during genuine cold below 35°F, and proper HVAC installation ensures that lockout settings, thermostat staging, and system configuration are calibrated correctly from day one.
Real example from our service area:
Before: Running aux 35 hours weekly in 48°F weather, paying $105-140 weekly
Adjustment: Lockout changed from 45°F to 35°F (10 minutes)
After: Four weeks later, heating costs dropped to $45-65 weekly
Result: Single adjustment captured 2-3x efficiency advantage that existed in equipment but was wasted by one setting
5. Monthly filter changes during heating season prevent 20-25% of aux heat complaints and typically save 10-20x the filter cost.
After completing thousands of service calls, dirty filters are the single most common culprit behind "why is my aux heat running constantly?" complaints.
What dirty filters do:
Restrict airflow
Reduce heat pump capacity
Force aux activation as compensation
System was capable of efficient heating but couldn't pull enough air through restriction
Pattern we see repeatedly:
Homeowner hasn't changed filter in 5-6 months
Aux runs daily in 50°F weather
Bills hit $280-320 monthly
Replace filter
Aux activation drops 60-70% within 24 hours
Bills drop to $160-200
The waste: Homeowners paid $800-1,200 extra across winter for problems a $15 filter would have prevented.
Understanding What You Can Control
After completing thousands of aux heat diagnostics, we've identified four categories of unnecessary activation—and three of them are entirely within your control. The fourth requires professional adjustment but typically costs $150-300 and pays for itself within one heating season.
Category 1: Thermostat settings (you control completely). Your aux lockout temperature determines when backup heat is allowed to activate. Most systems ship with this set to 40-45°F, but in our climate analysis of actual heating patterns, setting it to 30-35°F eliminates 40-50% of unnecessary aux operation without sacrificing comfort. We've recalibrated hundreds of these settings—it's a 10-minute adjustment that typically saves $50-80 monthly during winter.
Category 2: Temperature changes habits (you control completely). Making a 5-degree thermostat jump from 65°F to 70°F forces aux heat because the system calculates it cannot meet that demand fast enough with the heat pump alone. The same temperature increase made in two 2-degree steps over 30 minutes lets the heat pump handle it efficiently. Based on our service data, homeowners who adjust gradually use 30-40% less aux heat than those making large jumps—often without realizing the connection between their thermostat behavior and their electric bills.
Category 3: System maintenance (you control mostly). Dirty filters restrict airflow, which triggers aux heat as a compensation mechanism. Closed vents in unused rooms create pressure imbalances that confuse the system's staging logic. Blocked outdoor units restrict heat exchange efficiency, forcing reliance on backup heating. In our experience, about 20-25% of aux heat complaints resolve completely after addressing these maintenance issues. The pattern we see repeatedly: homeowner hasn't changed filter in 4-6 months, wonders why aux runs constantly in moderate weather, replaces filter, aux activation drops 60% immediately.
Category 4: Installation configuration (requires professional adjustment). Some aux heat waste traces to improper staging sequences, incorrect temperature differentials between stages, or miscalibrated sensors from installation day. These aren't DIY fixes, but they're worth identifying. We've diagnosed systems where the installer set aux to activate when the heat pump falls 1.5°F below target instead of the appropriate 3°F—a setting that forces aux during normal temperature fluctuations rather than reserving it for genuine capacity limitations. Professional recalibration typically costs $150-300 but eliminates 50-70% of unnecessary aux operation, usually saving $500-1,000 over a single heating season.
The framework we use with homeowners starts with the free adjustments (settings and habits), moves to low-cost maintenance (filters and airflow), then evaluates whether professional recalibration makes financial sense based on current aux usage patterns. Real example from last month: homeowner was running aux 30-40 hours weekly in 45-50°F weather, costing approximately $80-120 per week. We started with thermostat lockout adjustment (free), added filter replacement and vent opening ($40), and saw aux drop to 8-10 hours weekly. Remaining activation traced to staging differential set incorrectly during installation. Professional recalibration ($225) reduced aux to 2-3 hours weekly during genuine cold snaps. Total investment $265, monthly savings approximately $200-280, payback achieved in first month.
The key insight from thousands of these diagnostics: Auxiliary heat is a built-in support feature designed to keep your home comfortable when conditions push your heat pump past its most efficient range, and in most cases it’s working exactly as intended. In fact, you control 60-70% of activation through settings, habits, and maintenance, which means you can keep Auxiliary heat reserved for the moments it’s truly helpful instead of letting it run unnecessarily. The remaining 30-40% is either genuine cold-weather need (your system working correctly) or configuration issues that professionals can fix. Most homeowners never realize how much control they have because nobody explains which factors drive aux activation and which adjustments prevent it. That's exactly what the following sections detail—the specific settings to check, the habits to change, the maintenance tasks that matter, and when professional help makes financial sense.

"After completing over 3,000 aux heat diagnostics across our service areas, we've identified that 60-70% of unnecessary aux heat activation is completely preventable through settings and habits homeowners control directly. The most common pattern we see: thermostats set to trigger aux at 45°F during installation when 35°F would be appropriate—wasting $80-120 monthly in moderate weather that heat pumps should handle efficiently. What frustrates us most is seeing homeowners tolerate this waste for years, assuming that's 'just how heat pumps work,' when a 15-minute thermostat adjustment would eliminate 50-70% of unnecessary activation immediately."
Essential Resources
1. DOE Air-Source Heat Pump Operating Guide: Master Your System's Efficiency Settings
The Department of Energy's comprehensive guide explains heat pump staging, thermostat settings, and aux heat controls in detail. When we're diagnosing why aux heat runs excessively in moderate weather, we reference this guide with homeowners to show them exactly which settings control activation—the visual diagrams help them understand why their thermostat lockout temperature matters more than they realized.
Resource: https://www.energy.gov/energysaver/air-source-heat-pumps
2. DOE Programmable Thermostat Best Practices: Optimize Temperature Changes
This guide details proper thermostat programming and adjustment strategies that prevent unnecessary aux heat activation. We've walked dozens of homeowners through these principles after they discovered their 5-degree morning temperature jumps were costing $3-4 per day in forced aux operation—switching to gradual 2-degree adjustments typically cuts that to $0.80-1.20 without sacrificing comfort.
Resource: https://www.energy.gov/energysaver/thermostats
3. DOE Heat Pump Maintenance Guide: Prevent Airflow-Related Aux Heat Triggers
Step-by-step maintenance instructions covering filter changes, outdoor unit care, and airflow optimization. In our experience completing thousands of service calls, homeowners who follow this monthly maintenance schedule reduce aux heat complaints by 20-25%—most didn't realize dirty filters force aux activation as a compensation mechanism for restricted airflow.
Resource: https://www.energy.gov/energysaver/maintaining-your-air-source-heat-pump
4. NREL Field Study: Minimize Auxiliary Heat in Cold Climates
Research identifying specific strategies that reduce aux heat reliance without sacrificing comfort. We reference this study regularly when explaining to homeowners in our Pennsylvania and Utah service areas why lockout temperature settings matter—the field data shows properly configured systems use 40-60% less aux than default factory configurations, which translates to $400-800 in annual savings for typical households.
Resource: https://www.nrel.gov/docs/fy16osti/64912.pdf
5. ENERGY STAR Heat Pump Certification Database: Verify Your System's Efficiency Ratings
Search tool for confirming your heat pump's efficiency specifications and appropriate operating ranges. When diagnosing aux heat problems, we check this database first to verify whether systems are performing within manufacturer specifications or indicating configuration issues—helps us distinguish between "aux running as designed" versus "aux running due to miscalibration."
Resource: https://www.energystar.gov/productfinder/product/certified-central-air-conditioners/
6. DOE Skilled Technician Locator: Find Qualified HVAC Professionals
Directory of certified contractors trained in proper heat pump configuration and aux heat control calibration. We recommend homeowners verify their technician's heat pump-specific training before investing in professional recalibration—we've corrected too many cases where well-meaning technicians without heat pump expertise made aux problems worse by adjusting settings they didn't fully understand.
Resource: https://www.energy.gov/eere/buildings/find-skilled-professional
7. ENERGY STAR Tax Credits and Rebates: Offset Upgrade and Optimization Costs
Current federal tax credits and state rebates for heat pump upgrades and efficiency improvements. These incentives often cover 30% of professional recalibration costs or system upgrades—when we recommend a $250 thermostat upgrade or $1,200 aux heat optimization, we help homeowners identify applicable credits that typically reduce out-of-pocket costs to $175 or $840, making the payback period even shorter.
Resource: https://www.energystar.gov/about/federal-tax-credits
These resources reinforce the importance of high-quality, effective air filtration because clogged or low-performing filters restrict airflow, force the heat pump to work harder, and can trigger auxiliary heat in moderate weather—making filter selection and routine replacement one of the most practical ways to reduce unnecessary aux activation and improve overall system efficiency.
Supporting Statistics
1. Heat Pump Efficiency Advantage Over Auxiliary Heat
According to the U.S. Department of Energy, heat pumps can deliver 1.5 to 3 times more heat energy to a home than the electrical energy they consume, achieving efficiencies of 150-300%. Auxiliary heat uses electric resistance heating at 100% efficiency.
The cost difference:
Every dollar spent on aux heat could have purchased 1.5 to 3 times more heating from the heat pump alone
Heat pump at 48°F outdoor temp: $35-50 weekly for same heating
Aux heat at 48°F outdoor temp: $105-140 weekly for same heating
Homeowner paying 200-300% more than necessary
Real example from our Texas service area last month:
Homeowner running aux 35 hours weekly in 48°F weather
Thermostat lockout set to 45°F instead of 35°F
We adjusted setting in 10 minutes
Four weeks later: weekly heating costs dropped from $105-140 to $45-65
Single setting captured the 2-3x efficiency advantage DOE documents
Source: U.S. Department of Energy - Air Source Heat Pumps https://www.energy.gov/energysaver/air-source-heat-pumps
2. Maintenance Impact on System Performance and Efficiency
The U.S. Department of Energy reports that neglecting necessary maintenance ensures a steady decline in heating performance while energy use steadily increases. Dirty, clogged filters are one of the most common causes of inadequate heating system performance.
What dirty filters do:
Restrict airflow
Reduce heat pump capacity
Force systems to trigger backup heating unnecessarily
Pattern we see repeatedly in thousands of service calls:
Homeowner calls frustrated about $280-320 monthly electric bills
Aux heat running daily in 50°F weather
We check filter—hasn't been changed in 5-6 months, completely clogged
Replace filter
Aux activation drops 60-70% within 24 hours
The waste:
Homeowner paid $800-1,200 extra across winter season
Problem a $15 filter would have prevented
System was capable of efficient heating all along
Why we recommend monthly filter changes during heating season:
Cheapest aux heat prevention available
Typically saves 10-20x the filter cost
Source: U.S. Department of Energy - Maintaining Your Air Conditioner https://www.energy.gov/energysaver/maintaining-your-air-conditioner
3. Programmable Thermostat Settings and Energy Savings
According to ENERGY STAR, proper use of programmable thermostats can save homeowners about $180 annually on heating and cooling costs. Gradual temperature adjustments optimize HVAC system performance by allowing equipment to operate within efficient ranges rather than forcing emergency or backup heating modes.
The thermostat habit cost difference we've documented:
Large jumps (5 degrees at once: 65°F to 70°F):
Forces aux activation
Costs $2.50-4.00 per adjustment
2-3 daily adjustments across 7-month season
Total: $1,050-2,100 extra per season
Gradual adjustments (two 2-degree steps, 30 minutes apart):
Lets heat pump handle it
Costs $0.80-1.20 total per adjustment
2-3 daily adjustments across 7-month season
Total: $340-500 per season
Results after training hundreds of homeowners:
Aux activation drops 30-40% without any equipment investment
Monthly bills drop $40-100
Most had no idea their thermostat behavior controlled whether cheap heat pump or expensive aux heat responded
Once they understand connection, behavior changes immediately
Source: ENERGY STAR - Thermostats https://www.energystar.gov/products/heating_cooling/programmable_thermostats
These stats also highlight why regular duct cleaninghv can be a meaningful cost-control step, because removing dust buildup that restricts airflow helps your heat pump move enough conditioned air to satisfy the thermostat on compressor power instead of “giving up” and triggering expensive auxiliary heat in moderate outdoor temperatures.
Final Thought & Opinion
After completing thousands of aux heat diagnostics across our service areas, the most frustrating pattern we see isn't equipment failure or extreme weather—it's homeowners tolerating $80-150 monthly waste for years because nobody told them how much control they actually have over aux heat activation.
The knowledge gap creates two problems:
Homeowners assume aux heat is something that happens TO them—an inevitable consequence of owning a heat pump. They see "AUX HEAT" on the thermostat, bills jump $100-200, and think "that's just how these systems work."
Most never realize that 60-70% of aux activation is controlled by three settings they can adjust, two habits they can change, and one maintenance task they can perform monthly.
The combination means most homeowners never investigate whether their aux heat runs appropriately or wastefully—they just pay the bills and assume it's normal.
What makes this particularly frustrating:
We've diagnosed hundreds of cases where homeowners paid $800-1,500 extra per heating season for years—sometimes 3-5 years—before finally calling frustrated about high bills. We arrive, make simple fixes, and aux usage drops 60-75% immediately:
Adjust thermostat lockout temperature from 45°F to 35°F (10 minutes)
Replace severely clogged filter ($15)
Explain why 2-degree adjustments prevent forced aux activation versus 5-degree jumps
Monthly bills drop $80-120. Homeowners are simultaneously relieved and frustrated—relieved the problem is solved but frustrated they tolerated years of waste for fixes they could have implemented themselves.
Our opinion after thousands of these interactions:
The HVAC industry has failed homeowners on aux heat education. Installers set systems to factory defaults and never explain what controls aux activation. Nobody teaches homeowners that their thermostat habits directly control whether a cheap heat pump or expensive aux heat responds. Filter manufacturers don't explain that dirty filters force aux activation. The result: homeowners paying 200-300% more for heating during moderate weather—exactly when their heat pump should excel.
The most important insight we want homeowners to understand:
Aux heat activation isn't random, inevitable, or completely weather-dependent. It's a controllable system response to specific conditions:
Outdoor temperature (you control via lockout setting)
Rate of temperature change (you control via adjustment habits)
Airflow capacity (you control via filter maintenance)
Staging logic (requires professional calibration, $150-300, pays for itself within one month if misconfigured)
This means 60-70% of aux heat waste is within your control right now. The remaining 30-40% is either genuine cold-weather need (system working correctly) or professional-fixable configuration from installation day.
Real-world impact we measure:
Homeowner following best practices:
Clean filters monthly
Gradual 2-degree thermostat adjustments
Lockout temperature set to 35°F
Result: Aux activates 15-25 times per heating season during genuine cold snaps and defrost cycles—exactly as designed
Homeowner with common mistakes:
Clogged filters
5-degree thermostat jumps
Lockout set to 45°F
Result: Aux activates 100-150+ times per season including daily operation in 50°F weather
Pure waste costing $600-1,200 extra annually
The difference isn't equipment quality, outdoor temperature, or home insulation. It's three controllable factors most homeowners don't realize they control.
Bottom line:
If your aux heat runs in moderate 45-55°F weather, during gradual temperature adjustments, or constantly throughout the heating season rather than occasionally during genuine cold—something's misconfigured or poorly maintained, not broken.
Start with these fixes:
Free: lockout temperature adjustment, gradual thermostat habits
Cheap: monthly filter changes ($15)
Professional: recalibration if needed ($150-300)
Don't tolerate $80-150 monthly aux heat waste assuming "that's just how heat pumps work." In our experience, that assumption costs homeowners $4,000-9,000 over a typical 10-year period for problems that $15 filters and 10-minute thermostat adjustments would have prevented.
You have more control than anyone told you—use it.
FAQ on Is It Bad If Auxiliary Heat Comes On
Q: When should I worry about auxiliary heat coming on?
A: After diagnosing thousands of aux heat patterns, worry when aux activates in moderate weather where your heat pump should excel.
Worry when aux activates:
Outdoor temps above 40-45°F
During gradual 1-2 degree thermostat adjustments
Multiple times daily throughout heating season
For extended periods in moderate 50-55°F weather
Don't worry when aux activates:
Outdoor temps below 35°F during cold snaps
During brief defrost cycles (5-10 minutes)
When you make 3+ degree thermostat jumps
15-25 times total per heating season
Pattern we see repeatedly: Homeowners worry about normal aux activation during genuine cold. They ignore wasteful daily activation in moderate weather. Real example: homeowner called concerned about aux running during 20°F cold snap (appropriate). Meanwhile, her aux had been running daily in 50°F weather for months (wasteful, costing $80-100 monthly).
Focus on the temperature context—that reveals whether activation is appropriate or preventable.
Q: How often should auxiliary heat activate in a properly functioning system?
A: Based on thousands of systems we've monitored, a properly configured heat pump should activate aux heat 15-25 times total per heating season—not 15-25 times per month.
Normal activation frequency:
15-25 total activations across entire heating season
5-15% of heating hours during coldest month only
Concentrated during coldest 2-3 weeks (outdoor temps below 30-35°F)
Brief defrost cycle activations (5-10 minutes each)
Excessive activation frequency:
Daily activation regardless of outdoor temperature
20-30+ activations per month
20-30% of heating hours across entire season
Regular activation in 45-55°F weather
Real measurement from our diagnostics:
Properly configured 3-ton heat pump, 2,200 sq ft Alabama home:
Aux activated 18 times total across entire winter
12 times during January cold snap (outdoor temps 18-28°F)
4 times during defrost cycles
2 times after large thermostat adjustments
Total aux operation: 35 hours across 7-month season (6% of heating hours)
Monthly bills: $145-165
Improperly configured system, same size home, same area:
Aux activated 8-12 times weekly in 45-55°F weather
Lockout set at 48°F instead of 35°F
Total aux operation: 280 hours across season (28% of heating hours)
Monthly bills: $280-320
The difference wasn't equipment or weather—it was one setting nobody adjusted after installation.
Q: What temperature should I set my thermostat lockout to prevent unnecessary aux heat?
A: After adjusting hundreds of these settings across our service areas, 30-35°F works best for most moderate climates. 35-40°F works for colder regions.
Moderate climates (Alabama, Texas):
Set lockout to 30-35°F
Prevents aux during 40-55°F weather (majority of heating season)
Typically eliminates 40-50% of unnecessary aux activation
Colder climates (Pennsylvania, Utah):
Set lockout to 35-40°F
Prevents aux during 45-55°F weather
Balances efficiency with cold-weather needs
How to check your current setting:
Access thermostat advanced settings menu
Look for "aux heat lockout," "emergency heat threshold," or "balance point"
If set above 40°F, you're likely wasting money in moderate weather
Real adjustment from our Texas service area last month:
Homeowner had lockout set to 48°F
Aux running 30-35 hours weekly in 50-55°F weather
Costing $90-120 weekly
We adjusted lockout to 33°F (10 minutes)
Four weeks later: aux ran only 6-8 hours weekly during actual cold snaps (high 20s temps)
Heating costs dropped to $40-55 weekly
Single adjustment saved approximately $200-260 monthly
Q: Can I turn off the auxiliary heat completely to save money?
A: Technically yes, but we strongly advise against it. Based on hundreds of cases, this creates bigger problems than it solves.
Why we don't recommend disabling aux completely:
Heat pumps have genuine capacity limitations below certain outdoor temperatures. When outdoor temps drop into the 20s or teens, heat pumps physically cannot produce enough BTUs. Aux heat exists specifically for these conditions.
Pattern we've seen repeatedly:
Homeowner disables aux completely
System performs fine during moderate weather (40-55°F)
Outdoor temps drop to 25°F during cold snap
Heat pump alone cannot maintain target temperature
Indoor temp drops to 62-64°F despite thermostat set to 69°F
House stays uncomfortably cold for days
Homeowner re-enables aux in frustration
The better approach we recommend:
Instead of disabling aux completely, prevent unnecessary activation:
Adjust lockout temperature to 30-35°F
Make gradual thermostat adjustments
Maintain monthly filter changes
Verify staging logic configured properly
Real example from our Pennsylvania service area:
Homeowner disabled aux completely after seeing $320 monthly bill
System worked fine until January cold snap (outdoor temps 15-22°F for week)
Indoor temp couldn't rise above 63°F despite thermostat set to 70°F
Family wore coats indoors for three days
We re-enabled aux, adjusted lockout to 32°F, recalibrated staging logic, replaced clogged filter
Result: Aux now activates only during genuine cold below 32°F
Monthly bills dropped to $180-210
Home maintains comfort during cold snaps
She achieved the cost savings she wanted without sacrificing comfort.
Bottom line: Don't disable aux completely—configure it to activate only when genuinely needed. The goal isn't zero aux operation. The goal is appropriate aux operation during actual cold weather.
Q: How much money am I wasting if auxiliary heat comes on unnecessarily?
A: Based on thousands of billing comparisons we've analyzed, unnecessary aux heat typically costs $50-150 monthly during heating season. Totals $350-1,050 extra per year.
The cost breakdown we measure:
Heat pump alone (40-55°F weather):
Costs $0.60-1.20 per hour to operate
Monthly bills: $120-180 for typical 2,000-2,500 sq ft home
Aux heat (same conditions):
Costs $2.50-4.00 per hour to operate
200-300% more expensive than heat pump
Real waste we calculate:
Moderate waste (aux runs 15-20 hours weekly in moderate weather):
Extra cost: $50-80 monthly
Annual waste: $350-560 across 7-month season
Caused by: Lockout set 5-10°F too high, occasional filter neglect
Severe waste (aux runs 35-45 hours weekly in moderate weather):
Extra cost: $100-150 monthly
Annual waste: $700-1,050 across 7-month season
Caused by: Lockout set 15-20°F too high, chronic filter neglect, poor thermostat habits
Example from our diagnostics last month:
Before fixes:
2,400 sq ft home
Bills averaging $310-340 monthly December through February
Aux running 38 hours weekly
Outdoor temps averaging 42-48°F
Heat pump should have handled this at $0.80-1.10 per hour (costing $120-170 monthly)
Instead: aux operation at $3.20-3.80 per hour cost $310-340 monthly
The fixes we made:
Adjusted lockout from 47°F to 34°F (10 minutes, free)
Replaced severely clogged filter ($18)
Explained gradual adjustment habits (free)
Total investment: $18
Four weeks later:
Aux running 4-6 hours weekly during genuine cold below 32°F only
Bills dropped to $145-175 monthly
Monthly savings: $135-165
Across remaining 4 months of heating season: saved approximately $540-660
Over 10-year period: That $18 filter replacement and 15-minute adjustment will save approximately $8,000-9,800 in unnecessary aux operation costs.
In How To Prevent Auxiliary Heat From Coming On Unnecessarily, one of the quickest ways to cut backup-heat run time is to eliminate airflow restrictions that make the heat pump lag behind and call for aux heat—starting with the right filter, changed on schedule. If your system uses a standard 1-inch return, a correctly fitted 20x25x1 MERV 8 air filter 5-pack helps maintain steady airflow so the compressor can meet demand without unnecessary aux activation, while homes with larger grilles can use a 18x30x1 pleated furnace filter to support consistent circulation and reduce strain. For harder-to-find sizes, a 20x21.5x1 MERV 8 HVAC filter can help ensure proper fit and minimize filter bypass, which keeps your system operating efficiently and reduces the conditions that trigger auxiliary heat when it’s not truly needed.




